Feature
Used for distributed Solar PV
● Reflux Monitoring
● Connected with Load Line through CTs
● Directly connect with inverters
Bidirectional Power Metering
● Active Power Metering
● Reactive Power Metering
RS485 Communication
● MODBUS-RTU Protocol
● Communicate with Inverter to realize anti-reflux Function
Paired with external CTs or Rogowski Coil
● Rated Current of CTs: up to 300A
● Rated Current of Rogowski Coil: up to 20000A
LCD Display
● Parameter Display
● Programming Interface
Keypads HMI for Programming
● Parameter Display Setting
● Communication(address, baud rate and etc.)
● Wiring: 3P3W,3P4W
Wiring Diagram
3P4W Wiring of ACR10R-DxxTE4 with external CTs
Particular Application
Solor PV Power Distribution Monitoring Solution
ACR10R-DxxTEx Practical Utility In Distributed Solar PV
Function
Function/Model |
ACR10RH-DxxT(R)E4 ACR10RH-DxxT(R)E3 |
|
Display mode |
LCD(Field LCD) |
■ |
Measuring parameter |
Current/voltage/frequency/power facto |
■ |
Active power/reactive power/apparent power |
■ |
|
Four quadrant electric energy measurement |
■ |
|
Maximum demand |
□ |
|
Multiple rate electric energy measurement |
□ |
|
Power quality monitoring |
Total harmonic content |
■ |
subharmonic(2-31 times) |
■ |
|
Data logging |
Incident record |
□ |
Display mode |
Alarm |
□ |
Built-in clock |
□ |
|
Communication |
RS485 interface |
■ |
Optional function (choose one) |
J(2DO) |
A1+(B1 or C1) (4DI+2DO or 4DI+EP)* |
K(4DI) |
||
pulse(2channels) |
Note:
1、“■”is standard allocation function,“□”is matching function,Above instrument stanfard 1 channel RS485 communication;
2、Terminal connection mode corresponding to A1/B1/C1 and so on in selection function;
3、Pulse output and relay output can not be selected at the same time;
4、When you select an event loggong feature,you must configure the DI or DO
Technical parameters |
Index |
|||
Input |
Net work |
3-phase 3-wire,3-phase 4 wire |
||
|
Frequency |
45~65Hz |
||
|
Voltage |
Rating:AC 57.7V/100V(100V)、220V/380V(400V) |
||
|
|
Overload:1.2-foldrating (continuous);2-fold rating/1second |
||
|
|
Consumption:<0.2VA |
||
|
Current |
Rating:80A,120A,200A .etc (See specific product specifications, special parameters can be customized) |
||
|
|
Overload:1.2-fold rating(continuous); 10-fold rating/1 second |
||
|
|
Consumption:< 0.2VA |
||
Output |
Electric energy |
Output mode:Open-collector photocoupler pulse,two way output |
||
|
|
Three-phase |
Pulse constant :4000,8000imp/kWh |
|
|
Communication |
RS485 interface, Modbus-RTU Protocol |
||
|
Display mode |
LCD |
||
Function |
Switching |
Input |
Four way dry contact input |
|
|
|
Output |
Output mode: two way relay nO contact output |
|
|
|
|
Contact capacity:AC 250V/3A、DC 30V/3A |
|
Measuring accuracy |
Frequency0.05Hz、reactive electric energy1class、other 0.5class |
|||
Power supply |
AC85~265V or DC100~350V;DC24V(±10%);DC48V(±10%) Consumption≤10VA |
|||
Safety |
Power-frequency withstand voltage |
Power frequency withstand voltage between Auxiliary power and switch volume output and current input and voltage input and communication and pulse output and switch volume input terminal is AC2kV 1min; Power frequency withstand voltage between auxiliary power and switch volume output and current input voltage input terminal is AC 2kV/1min; Power frequency withstand voltage between communication and pulse output and switch volume input terminal is AC 1kV/1min; |
||
|
Insulation resistance |
Input,Output terminal to housing>100MΩ |
||
Environment |
Working temperature:-10℃~+55℃;Storage temperature:-20℃~+70℃ Relative humidity:5%~95% No condensation;Altitude:≤2500m |