Acrel AC/DC 0-1000A Open-loop Hall Effect Transducer AHKC-EKB

 

 

  •  Rated Input: 0~±1000A DC or 0~1000A AC
  •  Rated Output: 0~±5/±4Vdc
  •  Aperture: φ40mm
  •  Power Supply: ±12~±15Vdc
  •  Accuracy: Class 1.0
  •  Response Time: ≤5us
  •  Installation: Clamp on (Split-core) measuring cable and screw fixed on panel
  •  Standard&Certificate: CE; IEC; LVD
description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Description

Feature

 
 

Dimension(unit:mm)

 
 

 

Wiring Digram

 
 

Clamp-on (Split-core) Installation on Measuring DC Cable

Wiring of Auxiliary Power Supply Input&Transduced Signal Output

Technical parameters

Main Parameters

Parameter

Description&Value

Rated Input

 0~±(50-1000)A DC or 0~(50~1000)A AC

Rated Output

 ±5Vdc/±4Vdc

Accuracy

 Class 1.0

Power Supply

 ±15Vdc (allow ±20% fluctuation%)

Consumption

 ≤0.5W

Zero Offset Voltage

 ±20mV

Offset Voltage Drift

 ≤±1.0mV/℃ 

Linearity

 ≤0.2%FS

Response Time

 ≤5us

Bandwidth

 0~20kHz

Isolation Voltage

 3.5kV/50Hz/1min

 

Environment

Condition

Description&Value

Temperature

 Operating Temperature: -40℃~+85℃;  Storage Temperature: -40°C ~+85°C

Humidity

 ≤95%RH,no condensation,without corrosive gas

Altitude

 ≤ 2000m

Download
  • CE of AHKC-EKB
  • IEC of AHKC-EKB
  • LVD of AHKC-EKB
  • AHKC-EKB Manual
  •  
  •  
  •  
  •  