Measurement: Up to 4-channel 3-phase kWh, kVarh, Current, Power, 2~31st Harmonic and etc
Voltage Rating: 3x220V/380V AC (3P4W)
Current Rating: 5A, 100A, 400A or 600A AC (with external CTs)
Frequency: 45~65Hz
Communication: RS485 (MODBUS-RTU)
Display: LCD
Multi-circuits Monitoring
● Monitor up to 4×3-phase circui
● External CTs Connectwith ADW210 Main Body thrrough RJ12 Interfacets in total
● Paired CTs with specs of 5A/1.25mA; 100A/20mA; 400A/100mA or
600A/100mA
Expanded Communication Module --- AWT100
● 4G (Global general module)
● WiFi
● LoRaWAN
● LoRa
● NB-IoT
Cable Temperature&Residual Current Measurement Module --- MTL
● Temperature Measurement:-20℃~+100℃
● Residual Current Measurement:10~3000 mA
● Accuracy:Temperature:± 2℃; Residual Current:1% (Class 1)
DO/DI Switch Extra Function Module --- MK
● 12 channel DI (Digital Input)
● 4 channel DO (Digital Output)
1.System support all the meters across the country whose data has been sent to cloudserver through 4G,WiFi or Ethernet.
2.Remote meter reading and data collection.
3.Provide loT APP for mobile phone side and loT WEB for PC side
4.Generate energy data report of daily, monthly and annually period with year-on-yeay andperiod-on-period energy analysis.
5.Provide various alarm function to ensure a stable operation of the system and protect youlproperty.
6.Offer 3-month free trial of system with full technical support as for a test phase or pilotproject.
Remark:
1AcrelloT EMS WEB(For PC users):http://iot.acrel-eem.com/
2AcrelloT EMS APP(For mobile Users):https://play.google.com/store/apps/details?id=com.acrel.iotems
3.Test Account: AcrePassword:123456
Prototype Function
Function |
Description |
Energy |
kWh (positive and negative) |
kvarh (positive and negative) |
|
A,B,C three-phase positive kWh |
|
Electric Parameter |
U, I, P, Q, S, PF, Hz |
Harmonic |
2-31st voltage and current harmonic |
Communication |
RS485 (MODBUS-RTU); baud rate 1200~38400 |
Expanded Module Function
Expanded Module |
Description |
|
AWT100 |
4G (Global general module) |
|
2G |
||
LoRaWAN (868 MHz, 923MHz) |
||
LoRa (460~510 MHz) |
||
NB-IoT |
||
-MK |
12 × DI (input) |
Dry contact input with built-in power supply |
4 × DO (output) |
Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A |
|
Power Supply |
DC 12V;consumption:≤1W;RJ45 interface |
|
Communication |
RJ45 interface; MODBUS-RTU (communication with main body) |
|
-MTC |
Temperature Measurement |
-20℃~+100℃ |
Residual Current Measurement |
10~3000 mA |
|
Accuracy |
Temperature:± 2℃; Residual Current:1% (Class 1) |
|
Power Supply |
DC 12V;consumption:≤1W;RJ45 interface |
|
Communication |
RJ45 interface; MODBUS-RTU (communication with main body) |
Technical Parameters (Prototype/Main body)
Parameters |
Description |
|
Input |
Voltage |
AC 3×220V/380V |
Overload: 1.2 times of rated value (continuous); 2 times of rated |
||
Power consumption:≤ 0.5VA |
||
Current |
AC 5A、100A、400A、600A;(external open-type CT) |
|
Overload: 1.2 times of rated value (continuous); 10 times |
||
Power consumption:≤ 0.5VA |
||
Frequency |
45~65Hz |
|
Measuring |
Voltage&Current |
Class 0.5 |
Active Power |
Class 1 |
|
Reactive Power |
Class 2 |
|
Frequency |
0.05Hz |
|
2~31st harmonic |
± 1% |
|
Auxiliary Power |
AC/DC 85~265V;consumption≤10VA; |
|
EMC |
Better than grade 3 |
|
Safety |
Withstand Voltage |
>AC 2000V/1min |
Insulation Resistance |
>100MΩ |
|
Environment |
Working Temperature |
-20℃~+60℃ |
Storage Temperature |
-40℃~+70℃ |
|
Humidity |
≤95% (No condensation) |
|
Altitude |
≤2500m |
Technical Parameters (paired Current Transformer)
Paired CT |
Primary Current |
Secondary Current |
Aperture(Hole size) |
Accuracy Class |
AKH-0.66/K-φ10N |
5A |
1.25mA |
10mm |
Class 0.5 |
AKH-0.66/K-φ16N |
100A |
20mA |
16mm |
Class 0.5 |
AKH-0.66/K-φ24N |
400A |
100mA |
24mm |
Class 0.5 |
AKH-0.66/K-φ36N |
600A |
100mA |
36mm |
Class 0.5 |
AKH-0.66-L-45 |
/ |
/ |
/ |
Class 1 |