Acrel ADW200 Multi-Chanel 3 phase Energy Meter

 

 

● Mearsure up to 4 circuit 3 phase


● Mearsure all electric parameters


● Split core open loop CTs


● External function module, such as MK(switching inputs and outputs), MTL(temperature measurement and leakage current measurement), AWT100(wireless communication)

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Description

Function

 
 

 

◊ Accuracy

Active power: Class 1

Reactive power: Class 2

 

◊ Frequency

Range: 50 - 60Hz

 

◊ Pulse output

Active pulse output and reactive pulse output

 

◊ Consumption

<0.5VA(Single phase)

 

 

 

 

 

◊ Dimension (L*W*H)

Panel size (L×W): 72*97.7*36 mm

 

◊ Installation

Din 35mm

 

◊ Wireless:

Transmission on 470MHz and maximum distance

in open space is 1km; 2G; NB

 

◊ Starting current: 4‰lb

 

 

Front panel

 
 

 

 

 

 

① U / Pulse / DO / DI / Communication / Auxiliary Power Supply

② Brand

③ Model Number

④ Indicator light

⑤ CH1, CH2, CH3, CH4 for current / extension module interface

 
 
 
 
 
 
 
 
 

Installation Instruction

 
 

 

Network

 
 

Parameter

Prototype Function

Function

Description

Energy
Measurement

kWh (positive and negative)

kvarh (positive and negative)

A,B,C three-phase positive kWh

Electric Parameter

U, I, P, Q, S, PF, Hz

Harmonic

2-31st voltage and current harmonic

Communication

RS485 (MODBUS-RTU); baud rate 1200~38400

 

Expanded Module Function

Expanded Module

Description

AWT100
Communication
Module

4G (Global general module)

2G

LoRaWAN (868 MHz, 923MHz)

LoRa (460~510 MHz)

NB-IoT

-MK
Swtich
Module

12 × DI (input)

Dry contact input with built-in power supply

4 × DO (output)

Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A

Power Supply

DC 12V;consumption:≤1W;RJ45 interface

Communication

RJ45 interface; MODBUS-RTU (communication with main body)

-MTC
Temperature
&
Residual Current
Measuring
Module

Temperature Measurement

-20℃~+100℃

Residual Current Measurement

10~3000 mA

Accuracy

Temperature:± 2℃;   Residual Current:1% (Class 1)

Power Supply

DC 12V;consumption:≤1W;RJ45 interface

Communication

RJ45 interface; MODBUS-RTU (communication with main body)

 

Technical Parameters (Prototype/Main body)

Parameters

Description

Input

 

Voltage

AC 3×220V/380V

Overload: 1.2 times of rated value (continuous); 2 times of rated
value / 1s

Power consumption:≤ 0.5VA

 

Current

AC 5A、100A、400A、600A;(external open-type CT)

Overload: 1.2 times of rated value (continuous); 10 times
of rated value / 1s

Power consumption:≤ 0.5VA

Frequency

45~65Hz

Measuring
Accuracy

Voltage&Current

Class 0.5

Active Power

Class 1

Reactive Power

Class 2

Frequency

0.05Hz

2~31st harmonic

± 1%

Auxiliary Power

AC/DC 85~265V;consumption≤10VA;

EMC

Better than grade 3

Safety

Withstand Voltage

>AC 2000V/1min

Insulation Resistance

>100MΩ

Environment

Working Temperature

-20℃~+60℃

Storage Temperature

-40℃~+70℃

Humidity

≤95% (No condensation)

Altitude

≤2500m

 

Technical Parameters (paired Current Transformer)

Paired CT

Primary Current

Secondary Current

Aperture(Hole size)

Accuracy Class

AKH-0.66/K-φ10N

5A

1.25mA

10mm

Class 0.5

AKH-0.66/K-φ16N

100A

20mA

16mm

Class 0.5

AKH-0.66/K-φ24N

400A

100mA

24mm

Class 0.5

AKH-0.66/K-φ36N

600A

100mA

36mm

Class 0.5

AKH-0.66-L-45
(for residual current)

/

/

/

Class 1

Download
  • CE of ADW200 Series
  • ADW200 Manual
  •  
  •  
  •  
  •  

CONTACT US