Function
ASCB1 Series Intelligent MCB Function
* Can monitor voltage, current, power, power and temperature in real time
* with over-pressure, under-pressure, overload, short circuit, over-current, and over-temperature and other protection functions
* With local manual lever, local electric control, local lock, remote control, timing control and other control function
* Guide rail type installation, optional pole number 1P / 2P / 3P / 4P
* Standard RS-485 (MODBUS) communication; optional buckle curve type C / D
Wiring Diagram
 
Network Diagram
FAQ
Q: Can the circuit breaker data be collected through RS485 communication?
A: The circuit breaker has its own RS485 communication interface, and it does not need to be equipped with an ASCB1-M gateway to access the customer system, but the customer needs to provide the circuit breaker with DC12V 12A auxiliary power supply
Q: How many circuit breakers can a gateway carry?
A: 16PCS
Q: How Gateways and Circuit Breakers are Networked?
A: The gateway and the circuit breaker are connected by a 4pin cable, a set of DC12V auxiliary power supply, and a set of RS485 communication lines.
The connection between the circuit breaker and the circuit breaker is the same.
One-key addressing operation through the gateway
Q: Does the circuit breaker need to be equipped with additional accessories?
A: 1. Internally integrate various sensor modules, including: current sensor, leakage transformer, temperature sensor, etc.;
Model |
ASCB1-63 |
ASCB1LE-63 |
|
Pole |
1P/2P/3P/4P |
2P/4P |
|
Grade of Shell |
63A |
||
Rated Voltage |
230V(1P/2P)、400V(3P/4P) |
||
Rated Current |
6A,10A,16A,20A,25A,32A,40A,50A,63A |
||
Instantaneous Unbuckle Type |
C/D |
||
Rated Short-circuit Breaking Capacity |
6000A |
||
Protect |
Over-current Protection |
Default 100% rated current alert, 110% Rated current trip with adjustable threshold |
|
Short-circuit Protection |
5-10 Rated current for 0.04 seconds for circuit break protection |
||
Overload Protection |
Default 100% rated power alert,110% Rated power trip with adjustable threshold |
||
Over-voltage Protection |
Default 110% rated voltage alert,120% rated voltage trip with adjustable threshold |
||
Under-voltage Protection |
Default 90% rated voltage alert,80% rated voltage trip with adjustable threshold |
||
Over-temperature Protection |
Default 80℃ alert,100℃ trip, the threshold is adjustable |
||
Leakage Protection |
No |
Default 20mA alert, 30mA trip, the threshold is adjustable |
|
Leakage self-Inspection |
No |
Manual button self-inspection |
|
Mechanical Life |
20000 times |
||
Electrical Life |
6000 times |
||
Levels of Protection |
IP20 |
||
Connection Capacity |
1-35mm² |
||
Elevation Requirements |
2000m |
||
Ambient Temperature |
-10℃~55℃,the average temperature at 24h was no higher than 40℃ |
||
Environmental Requirements |
No explosion hazard, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibration |
||
Relative Humidity |
At + 40℃, the relative humidity of the air is 50% and can have high relative humidity at lower temperatures |
||
Storage Temperature |
-20℃-70℃ |
||
Class of Pollution |
Ⅱ |
||
Installation Type |
Ⅲ |
||
Way to Installation |
Standard 35mm guide rail installation |