AMB Smart Alternating-current Bus Bar Monitor is a new development to cater for smart power bus bar. It consists of a feeding detection module and a tapping detection module and integrates functions of conventional power measurements, electricity monitoring, consumption assessment and control. It also boasts the online alarm function and enables the independent off-line operation. It monitors the bus bar interface temperature in real time.






|
Model |
Standard functions |
Optional functions |
|
AMB100-A |
(1) Full electrical measurements of three-phase AC circuit, 2nd to 63rd harmonic measurements, 1 leakage current, 8-way temperature, 1-way humidity maximum demand measurement, neutral current, potential difference measurement between the null line and the ground line, 2 digital inputs, 2 digital outputs |
/W(LORA) |
|
AMB100-A-P1 |
(2) Full electrical measurements of three-phase AC circuit, 2nd to 63rd harmonic measurements, 1 leakage current, 8-way temperature, 1-way humidity maximum demand measurement, neutral current measurement, 2 digital inputs, 2 digital outputs, discrete auxiliary power supply |
|
|
AMB110-A |
(1) Full electrical measurements of three-phase AC circuit, 2nd to 63rd harmonic measurements, 1 leakage current, 8-way temperature, 1-way humidity maximum demand measurement, neutral current measurement, potential difference measurement between the null line and the ground line, 2 digital inputs, 2 digital outputs |
|
|
AMB110-A-P1 |
(2) Full electrical measurements of three-phase AC circuit, 2nd to 63rd harmonic measurements, 1 leakage current, 8-way temperature, 1-way humidity, maximum demand measurement, neutral current measurement,2 digital inputs, 2 digital outputs, discrete auxiliary power supply |
|
|
AMB120 |
8-way temperature |
|
Measured parameters |
Voltage, current, frequency, active power, inactive power,power factor, active energy, inactive energy, 2nd-63rd harmonic, temperature, leakage |
||
|
Voltage |
Rated value |
3x220/380VAC |
|
|
Range |
±20% |
||
|
Overloading |
1.2 times than the rated voltage value continuously or 2 times than the rated voltage value instantaneously per second |
||
|
Current |
CT |
AMB100-A: 5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mA AMB110-A: 100A/20mA |
|
|
Range |
1%-120% |
||
|
Overloading |
1.2 times than the rated current value continuously or 10 times than the rated current value instantaneously per second |
||
|
Input frequency |
45-65Hz |
||
|
Measurement accuracy |
Voltage/current:grade 0.2; active power/energy:grade 0.5; inactive power/energy:grade 1; temperature:±1℃ |
||
|
Auxiliary power supply |
AMB100/110-A(/W):triggered upon receipt of request signal AMB100/110-A(/W)-P1:follow the bus bar voltage |
||
|
Functions |
Temperature detection |
-20-150℃ |
|
|
Leakage |
0-1A |
||
|
Digital input |
2 dry-contact inputs |
||
|
Digital output |
2 relay outputs; contact capacity :3A/30VDC, 3A/250VAC |
||
|
Communication |
Via RS485/Modbus-RTU or LORA antenna |
||
|
Installation |
Use DIN35mm rail |
||
|
Protection |
IP20 |
||
|
Pollution level |
2 |
||
|
Environment |
Temperature/ humidity/ altitude
|
Working temperature:-20-60℃ Storage temperature:-25-70℃ Relative humidity:≤93% Altitude:≤2500m
|
|
|
Safety |
Insulation |
The minimum insulation resistance between all terminals and conductive components of the shell is 100MΩ. |
|
|
Withstanding voltage |
When a voltage of 2kV AC is applied between the voltage/ current input, relay output, RS485 port, auxiliary power supply and digital inputs, the leakage shall be less than 2mA and no breakdown or flashover shall occur in 1min. |
||
|
Electromagnetic immunity |
Electrostatic discharge immunity |
Class 4 |
|
|
Radio frequency electromagnetic immunity |
Class 3 |
||
|
Transient burst immunity |
Class 4 |
||
|
Surge immunity |
Class 4 |
||