Full Electric Parameters Measurement
● 3-phase (I, U, kW, kVar, kWh, Hz, cosφ)
● Current&Voltage Unbalance
● Harmonic (THD & 2~63rd)
● Real-time&Max Demand
● Extremum of this month&last month
● Zero-sequence Current
● 4-quadrant Energy
DO/DI Switch Function Module ---MD82
● 2 DO Relay Output
● 8 DI Digital Input
● Save up to 128 pcs DO/DI Data in Main Body
● Paired with MLOG to save more DO/DI Records
SD Card Data Storage Module ---MLOG
● Expand Number of SOE Storage
● Support Storage of SD Cards up to 32GB (standard 4GB)
Extra RS485 Communication Module ---MCM
● Interface: RS485 Interface
● Protocol: MODBUS-RTU
● Support Salve&Master Mode
Ethernet Communication Module ---MCME
● Interface: RJ45 Interface
● Protocol: MODBUS-TCP/HTTP/DHCP/SMTP
● Could Serve as Serial Server
● Plus 1 Extra RS485 Interface
PROFIBUS-DP Communication Module ---MCMP
● Interface: PROFIBUS-DP Interface
● Protocol: PROFIBUS-DP
● Plus 1 Extra RS485 Interface
SOE Function (Main Body)
● Alarm Record (128 pcs records of 66 kinds&13 categories)
● DO/DI Record (128 pcs DO/DI records)
● Transient Record (800 pcs transient waveform records)
● Max Records pcs above could be expanded by SD Card
Multi-rate/Multi-tariff
● 4 Time zone
● 4 Tariff rate (Spike, Peak, Flat, Valley)
● 2 Time period list
● 14 Time period by day
Local Configuration
● Keypads HMI for Programming
● Setting through Adjustment Software
● Setting through WEB
● Setting through MODBUS communication
Function
Function |
Function description |
APM800 |
APM801 |
APM810 |
APM830 |
Parameters |
All parameters |
■ |
■ |
■ |
■ |
Four-quadrant energy |
■ |
■ |
■ |
■ |
|
Multi-rate energy |
□ |
□ |
□ |
■ |
|
Pulse output of energy |
Active/reactive |
■ |
■ |
■ |
■ |
Demand |
Real-time and maximum demand of I, P, Q,S (with time) |
■ |
■ |
■ |
■ |
Extreme value statistics |
Extremum of I, UL-L, UL-N, P, Q, S, PF, F, THDi, THDu in this month and last month (with time) |
■ |
■ |
■ |
■ |
Power quality |
Unbalance of I,UL-L,UL-N |
■ |
■ |
■ |
■ |
Voltage phase angle,current phase angle |
■ |
■ |
■ |
■ |
|
Total and 2nd-63rd harmonic content of voltage and current |
- |
- |
■ |
■ |
|
Voltage crest factor |
- |
- |
■ |
■ |
|
Telephone waveform factor |
- |
- |
■ |
■ |
|
Current K-factor |
- |
- |
■ |
■ |
|
Positive sequence, negative sequence, zero sequence voltage and current |
- |
- |
- |
■ |
|
Fundamental voltage and current |
- |
- |
- |
■ |
|
Waveform |
Waveform trace display |
- |
- |
- |
■ |
Fault waveform record |
- |
- |
- |
■ |
|
Alarm |
A total of 66 kinds of alarm types, each type can record the most recent 16 alarm records, support extended records by TF card |
■ |
■ |
■ |
■ |
Event |
Record the most recent 128 event records, support extended records by TF card |
■ |
■ |
■ |
■ |
Communication |
RS485(Modbus-RTU) |
■ |
■ |
■ |
■ |
I/O |
2DI+2DO |
■ |
■ |
■ |
■ |
Function |
Function description |
APM800 |
APM801 |
APM810 |
APM830 |
|
Optional functions |
MD82 |
8DI+2DO |
■ |
■ |
■ |
■ |
MLOG |
TF card |
■ |
■ |
■ |
■ |
|
MA84 |
8AI+4AO |
■ |
■ |
■ |
■ |
|
MCM |
1 RS485(Modbus-RTU),support master mode or slave mode |
■ |
■ |
■ |
■ |
|
MCMP |
1 Profibus(Profibus-DP) |
■ |
■ |
■ |
■ |
|
MCME |
1 Ethernet(Modbus-TCP,HTTP,DHCP) |
■ |
■ |
■ |
■ |
Technical Parameters
Technical Parameter |
Value |
|
Signal |
Connection |
3 phase 3 wire, 3 phase 4 wire |
Frequency |
45~65Hz |
|
Voltage |
Rated value: AC 100V,110V,400V,690V |
|
Overload: 1.2 times rated value(continuous); 2 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Current |
Rated value: AC 1A, 5A |
|
Overload: 1.2 times rated value(continuous); 10 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Measurement accuracy |
Voltage,current and power |
Class 0.5S (APM800,APM810) |
Active power |
||
Reactive power |
Class 2(APM800, APM810), Class 0.5(APM801,830) |
|
Harmonic |
1%(2~42nd),2%(43~63rd) |
|
Switch inputs |
Passive contact inputs, built-in power supply |
|
Relay outputs |
Contact type: open contact in main part, changeover contact in module Contact capacity:3A/AC 250V 3A/DC 30V |
|
Pulse output of energy |
Output mode: Optocoupler pulse with open collector Pulse constant:4000(5A),8000(1A) imp/kWh |
|
Analog outputs |
DC 0~20mA,4~20mA,0~5V,1~5V output, accuracy class 0.5%, load resistance ≤ 500Ω |
|
Analog inputs |
DC 0~20mA,4~20mA,0~5V,1~5V input, accuracy class 0.5% |
|
Storage card |
Standard capacity:4G,TF card up to 32G capacity |
|
Communication |
RS485(Modbus-RTU) |
|
Profibus(Profibus-DP) |
||
Ethernet(Modbus-TCP,HTTP,DHCP) |
||
Auxiliary power supply |
Operating range: AC/DC 85V~265V or AC/DC 115~415V(P2) |
|
Power consumption: Power consumption of the main part ≤ 15VA |
||
Safety |
Insulation resistance |
>100MΩ |
Electromagnetic compatibility |
IEC 61000 standard (Level 4) |
|
Protection level |
IP54(Front) |
Technical Parameter |
Value |
Environment |
Operating temperature: -20 °C ~ +65 °C |
Storage temperature: -20°C~+70°C |
|
Relative humidity: ≤95%(no condensation) |
|
Altitude: ≤2500m |